Overview
The Model 168 Series are low range differential pressure transducers and transmitters in HVAC building automation, high accuracy pharmaceutical and health care facilities. It is with NEMA 4 (IP-65) rated aluminum enclosures, they are very rugged and very reliable. The Model 168 delivers reliable measurements below 0.05 inches of water.
Up to 15 PSI Proof Pressure on all Ranges
Miswiring Full Protection
Unsymmetrical Bidirectional Pressure Ranges
True Zero Output for Voltage Unit
Accuracy: ±0.25%, ±0.40% or ±0.60% of span
Differential Pressure Ranges:
Unidirectional: 0.10 in.W.C. to 100.00 in.W.C.
Bidirectional: ±0.10 in.W.C. to ±50.00 in.W.C.
NEMA 1; Die-cast aluminum
Mounting: surface mount
Output signal: current or voltage
HVAC and VAV Control
Clean Room and Isolation Rooms
Duct Static Pressure Measurement
Draft Control
Furnace Air Flow Control
Power Plant Air Flow Monitor and Control
Certificates & Approvals
CE
RoHS